Dimensions (W x L x H)50.1 mm x 107.3 mm x 57.5 mm
Grid dimension50.1 mm
Type of mountingScrew-clamped
Product weight121 g
Mounting positionoptional
Ambient temperature-20 °C ... 50 °C
Note on ambient temperatureObserve ambient temperature derating according to IEC 61131-2:2017
Storage temperature-20 °C ... 70 °C
Relative air humidity5 - 95% Non-condensing
Nominal altitude of use<= 2000 m ASL (> 79.5 kPa)
Max. installation height3500 m
Note on max. installation heightObserve ambient temperature derating according to IEC 61131-2:2017
Corrosion resistance class CRC1 - Low corrosion stress
Vibration resistanceTransport application test with severity level 2 to FN 942017-4 and EN 60068-2-6
Note on vibration resistanceSG1 on H-rail SG2 on direct mounting Transport application test with severity class 1 to FN 942017-4 and EN 60068-2-6
Shock resistanceShock test with severity level 2 to FN 942017-5 and EN 60068-2-27
Note on shock resistance30 g/11 ms to EN 60068-2-27 SG1 on H-rail SG2 on direct mounting Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27
Protection classIII
Pollution degree2
Overvoltage categoryII
Max. cable length30 m inputs
LABS (PWIS) conformityVDMA24364-B2-L
Fire test materialUL94 V-0 (housing)
Note on materialsRoHS-compliant Free of halogen Free of phosphoric acid ester
Material coverPBT-reinforced
Material screwsNickel-plated steel
Material threaded sleeveHigh-alloy stainless steel
Material o-ringFPM
Diagnostics via LEDDiagnostics per module Status per channel
Diagnostics per internal communicationWire break Communication fault Short circuit/overload Parameter errors Parameterisation error Overload at analogue inputs Upper limit value violated Electronics/sensors overvoltage Overflow/underflow Lower limit value not observed Electronics/sensors unde
Max. address volume, inputs8 Byte
Channel parametersMeasured value smoothing Signal range Lower/upper limits Activation of linear scaling Unit for temperature measurement Hysteresis for monitoring measured values
Communication interface, protocolAP
Note regarding operating voltageSELV/PELV fixed power supplies required Note voltage drop
Note on nominal operating voltage DCProtected Extra-Low-Voltage to IEC 60204-1
Nominal DC operating voltage, electronics/sensors24 V
Permissible voltage fluctuations for electronics/sensors± 25%
Intrinsic current consumption at nominal operating voltage for electronics/sensorsTypically 34 mA
Power failure bridging10 ms
Reverse polarity protectionyes
Electrical connection input, functionAnalogue input
Electrical connection input, connection type4x socket
Electrical connection input, connector systemM12x1, A-coded to EN 61076-2-101
Electrical connection input, number of connections/cores5
Electrical connection input, connection pattern00995384
Number of inputs4
Behaviour after end of overload of the sensor supplyAutomatic return
Fuse protection of inputs (short circuit)Internal electronic fuse per module
Max. residual current of inputs per module1 A
Electrical isolation of inputs between channelsno
Electrical isolation of inputs between channel – internal communicationyes
Measured variableVoltage Current Temperature Resistor
Note on the measured variableTemperature: PT100 and NI100 supported
Data format15 bits + prefix Linear scaling
analog input-10 - 10 V -5 - 5 V 0 - 10 V 1 - 5 V 0 - 20 mA 4 - 20 mA 0 - 500 Ohm
Repetition accuracy±0.025% at 25°C
Basic error limit at 25 °C±0.1% for voltage ±0.1% for current ±0.4% for temperature ±0.2% for resistor
Operating error limit related to the ambient temperature range±0.15% for voltage ±0.15% for current ±0.9% for temperature ±0.35% for resistor
Max. power supply per channel0.5 A