Dimensions (W x L x H)50.1 mm x 107.3 mm x 57.5 mm
Grid dimension50.1 mm
Type of mountingScrew-clamped
Product weight98 g
Mounting positionoptional
Note on ambient temperatureObserve ambient temperature derating according to IEC 61131-2:2017
Storage temperature-20 °C ... 70 °C
Relative air humidity5 - 95% Non-condensing
Nominal altitude of use<= 2000 m ASL (> 79.5 kPa)
Max. installation height3500 m
Note on max. installation heightObserve ambient temperature derating according to IEC 61131-2:2017
Corrosion resistance class CRC1 - Low corrosion stress
Vibration resistanceTransport application test with severity level 2 to FN 942017-4 and EN 60068-2-6
Note on vibration resistanceSG1 on H-rail SG2 on direct mounting Transport application test with severity class 1 to FN 942017-4 and EN 60068-2-6
Shock resistanceShock test with severity level 2 to FN 942017-5 and EN 60068-2-27
Note on shock resistance30 g/11 ms to EN 60068-2-27 SG1 on H-rail SG2 on direct mounting Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27
Protection classIII
Pollution degree2
Overvoltage categoryII
Max. cable length30 m outputs 30 m inputs
LABS (PWIS) conformityVDMA24364-B2-L
Fire test materialUL94 V-0 (housing)
Note on materialsRoHS-compliant Free of halogen Free of phosphoric acid ester
Material coverPBT-reinforced
Material screwsNickel-plated steel
Material o-ringFPM
Diagnostics via LED(Outputs) Diagnostics per channel Power supply load (outputs) (Inputs-Outputs) Diagnostics per module (Inputs-Outputs) Status per channel
Diagnostics per internal communicationCommunication fault Short-circuit/overload in output signal Short circuit/overload in sensor supply Electronics/sensors overvoltage Load overvoltage Electronics/sensors undervoltage Load undervoltage
Max. address volume, inputs2 Byte
Max. address volume, outputs1 Byte
Number of outputs4
Module parametersConfiguration of voltage monitoring load supply PL Behaviour after short circuit/overload at the output
Channel parametersInput debounce time
Communication interface, protocolAP
Note regarding operating voltageSELV/PELV fixed power supplies required Note voltage drop
Note on nominal operating voltage DCProtected Extra-Low-Voltage to IEC 60204-1
Nominal operating voltage DC of load24 V
Permissible voltage fluctuation of load± 25 %
Nominal DC operating voltage, electronics/sensors24 V
Permissible voltage fluctuations for electronics/sensors± 25%
Intrinsic current consumption at nominal operating voltage for electronics/sensorsTypically 40 mA
Intrinsic current consumption at nominal operating voltage loadTypically 5 mA
Power failure bridging10 ms
Potential separation between the supply voltages electronics/sensor technology and load/valvesYes
Reverse polarity protectionyes
Electrical connection input, functionDigital input
Electrical connection input, connection type6 x socket
Electrical connection input, connector systemM12x1, A-coded to EN 61076-2-101
Electrical connection input, number of connections/cores5
Electrical connection input, connection pattern00995384
Number of inputs12
Characteristic for inputsTo IEC 61131-2, type 3
Switching levelSignal 0: <= 5 V Signal 1: >= 11 V
Switching logic for inputsPNP (positive switching) 2-wire sensors to IEC 61131-2 3-wire sensors to IEC 61131-2
Input debounce time3 ms (standard) 10 ms 20 ms
Behaviour after end of overload of the sensor supplyAutomatic return
Fuse protection of inputs (short circuit)Internal electronic fuse per module
Max. residual current of inputs per module1.8 A
Electrical isolation of inputs between channelsno
Electrical isolation of inputs between channel – internal communicationyes
Electrical connection output, functionDigital output
Electrical connection output, connection type2x socket
Electrical connection output, connector systemM12x1, A-coded to EN 61076-2-101
Electrical connection output, number of connections/cores5
Electrical connection output, connection pattern00995384
Characteristic for outputsAccording to IEC 61131-2, type 0.5
Switching logic for outputsPNP (positive switching)
Fuse protection of outputs (short circuit)Internal electronic fuse per channel
Behaviour after end of overload of the outputsNo automatic return
Output delay with ohmic loadSignal change 0->1: < 200 µs Signal change 1->0: < 200 µs
Max. residual current outputs per module2 A
Electrical isolation of outputs between channelsno
Electrical isolation of outputs between channel - internal communicationyes
Max. power supply per channel0.5 A