Dimensions (W x L x H)50.1 mm x 107.3 mm x 57.5 mm
Grid dimension50.1 mm
Type of mountingScrew-clamped
Product weight98 g
Mounting positionoptional
Ambient temperature-20 °C ... 50 °C
Note on ambient temperatureObserve ambient temperature derating according to IEC 61131-2:2017
Storage temperature-20 °C ... 70 °C
Relative air humidity5 - 95% Non-condensing
Nominal altitude of use<= 2000 m ASL (> 79.5 kPa)
Max. installation height3500 m
Note on max. installation heightObserve ambient temperature derating according to IEC 61131-2:2017
Corrosion resistance class CRC1 - Low corrosion stress
Vibration resistanceTransport application test with severity level 2 to FN 942017-4 and EN 60068-2-6
Note on vibration resistanceSG1 on H-rail SG2 on direct mounting Transport application test with severity class 1 to FN 942017-4 and EN 60068-2-6
Shock resistanceShock test with severity level 2 to FN 942017-5 and EN 60068-2-27
Note on shock resistance30 g/11 ms to EN 60068-2-27 SG1 on H-rail SG2 on direct mounting Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27
Protection classIII
Pollution degree2
Overvoltage categoryII
Max. cable length30 m outputs
LABS (PWIS) conformityVDMA24364-B2-L
Fire test materialUL94 V-0 (housing)
Note on materialsRoHS-compliant Free of halogen Free of phosphoric acid ester
Material coverPBT-reinforced
Material screwsNickel-plated steel
Material o-ringFPM
Diagnostics via LEDDiagnostics per channel Diagnostics per module Load power supply Status per channel
Diagnostics per internal communicationCommunication fault Short-circuit/overload in output signal Electronics/sensors overvoltage Load overvoltage Electronics/sensors undervoltage Load undervoltage
Max. address volume, outputs1 Byte
Number of outputs8
Module parametersConfiguration of voltage monitoring load supply PL Behaviour after short circuit/overload at analogue output
Communication interface, protocolAP
Note regarding operating voltageSELV/PELV fixed power supplies required Note voltage drop
Note on nominal operating voltage DCProtected Extra-Low-Voltage to IEC 60204-1
Nominal operating voltage DC of load24 V
Permissible voltage fluctuation of load± 25 %
Nominal DC operating voltage, electronics/sensors24 V
Permissible voltage fluctuations for electronics/sensors± 25%
Intrinsic current consumption at nominal operating voltage for electronics/sensorsTypically 40 mA
Intrinsic current consumption at nominal operating voltage loadTypically 5 mA
Power failure bridging10 ms
Potential separation between the supply voltages electronics/sensor technology and load/valvesYes
Reverse polarity protectionyes
Electrical connection output, functionDigital output
Electrical connection output, connection type8x terminal strip
Electrical connection output, connector systemSpring-loaded terminal
Electrical connection output, number of connections/cores4
Electrical connection output, connection pattern00997388
Electrical connection for output, conductor cross section0.25 mm² ... 1.5 mm²
Electrical connection for output, note on conductor cross section0.13 - 1.5 mm² for flexible conductors without wire ferrule
Electrical connection for output, AWG conductor cross sectionAWG24 - AWG16
Characteristic for outputsAccording to IEC 61131-2, type 0.5
Switching logic for outputsPNP (positive switching)
Fuse protection of outputs (short circuit)Internal electronic fuse per channel
Behaviour after end of overload of the outputsNo automatic return
Output delay with ohmic loadSignal change 0->1: < 200 µs Signal change 1->0: < 200 µs
Max. residual current outputs per module4 A
Electrical isolation of outputs between channelsno
Electrical isolation of outputs between channel - internal communicationyes
Max. power supply per channel0.5 A