Dimensions (W x L x H)45 x 170 x 35 mm
Type of mountingOn H-rail via accessories With through-hole
Max. number of modules56
Product weight186 g
Ambient temperature-20 °C ... 60 °C
Storage temperature-40 °C ... 70 °C
Relative air humidity5 - 95% Non-condensing
Degree of protectionIP65 IP67
Note on degree of protectionUnused connections sealed
Corrosion resistance class CRC1 - Low corrosion stress
Max. cable length50 m system communication
LABS (PWIS) conformityVDMA24364-B2-L
Cleanroom suitability, measured according to ISO 14644-14Element installed statically, no meaningful evaluation possible according to ISO 14644-1
CE mark (see declaration of conformity)To EU EMC Directive
UKCA marking (see declaration of conformity)To UK instructions for EMC
KC markKC-EMV
ApprovalRCM trademark c UL us listed (OL)
Certificate issuing authorityUL E239998
Note on materialsRoHS-compliant
Material housingPC Die-cast zinc, nickel-plated
Material o-ringFPM
Diagnostics via LEDDiagnostics per module Power supply, electronics/sensors Load power supply System diagnostics Service required
Diagnostics via busAPDD invalid Load switch-off Communication with AP module interrupted Electronics/sensors overvoltage Load overvoltage Electronics/sensors undervoltage Load undervoltage
Note on fieldbus interfaceTerminating resistor at socket possible
Fieldbus interfacePROFIBUS
Field bus, protocolPROFIBUS DP-V1
Fieldbus interface, functionIncoming bus connection
Field bus, connection typePlugs
Field bus, connection systemM12x1, B-encoded to EN 61076-2-101
Field bus, connection pattern5
Field bus interface, electrical isolationyes
Field bus interface, transmission rate1.5 Mbps 12 Mbit/s 187.5 kbit/s 19.2 kbit/s 3 Mbit/s 500 kbit/s 6 Mbit/s 9.6 kbit/s 93.75 kbit/s
Fieldbus interface 2, typePROFIBUS
Fieldbus interface 2, protocolPROFIBUS DP-V1
Fieldbus interface 2, functionOutgoing bus connection
Fieldbus interface 2, connection typeSocket
Fieldbus interface 2, connection technologyM12x1, B-encoded to EN 61076-2-101
Fieldbus interface 2, number of pins/wires5
Fieldbus interface 2, galvanic isolationyes
Fieldbus interface 2, transmission rate1.5 Mbps 12 Mbps 187.5 kbps 19.2 kbps 3 Mbps 500 kbps 6 Mbps 9.6 kbps 93.75 kbps
Max. address volume, inputs244 Byte
Max. address volume, outputs244 Byte
Configuration supportGSD file
Communication interface, functionSystem communication XF20 OUT / XF21 OUT
Communication interface, connection type2x socket
Communication interface, connection technologyM8x1, D-coded according to EN 61076-2-114
Communication interface, number of pins/cores4
Communication interface, protocolAP
Communication interface, screenedyes
Power supply, functionIncoming electronics/sensors and load
Power supply, connection typePlugs
power supply, connection systemM8x1, A-coded to EN 61076-2-104
Power supply, number of pins/wires4
Power transmission, functionOutgoing electronics/sensors and load
Power transmission, connection typeSocket
Power transmission, connection technologyM8x1, A-coded to EN 61076-2-104
Power transmission, number of pins/wires4
Note regarding operating voltageSELV/PELV fixed power supplies required Note voltage drop
Nominal operating voltage DC of load24 V
Permissible voltage fluctuation of load± 25 %
Nominal DC operating voltage, electronics/sensors24 V
Permissible voltage fluctuations for electronics/sensors± 25%
Max. power supply2 x 4 A (external fuse required)
Intrinsic current consumption at nominal operating voltage for electronics/sensorsTypically 80 mA
Intrinsic current consumption at nominal operating voltage loadTypically 5 mA
Power failure bridging10 ms
Reverse polarity protectionyes