Dimensions (W x L x H)30 x 102.5 x 35 mm
Type of mountingWith through-hole
Product weight81 g
Storage temperature-40 °C ... 70 °C
Relative air humidity5 - 95% Non-condensing
Degree of protectionIP65 IP67
Note on degree of protectionUnused connections sealed
Corrosion resistance class CRC1 - Low corrosion stress
Max. cable length30 m inputs 50 m system communication
LABS (PWIS) conformityVDMA24364-B2-L
Cleanroom suitability, measured according to ISO 14644-14Element installed statically, no meaningful evaluation possible according to ISO 14644-1
CE mark (see declaration of conformity)To EU EMC Directive
UKCA marking (see declaration of conformity)To UK instructions for EMC
KC markKC-EMV
ApprovalRCM trademark c UL us listed (OL)
Certificate issuing authorityUL E239998
Note on materialsRoHS-compliant
Material housingPC Die-cast zinc, nickel-plated
Material sealsNBR
Material o-ringFPM
Diagnostics via LEDDiagnostics per module Status per channel
Diagnostics per internal communicationShort circuit/overload in sensor supply Electronics/sensors overvoltage Electronics/sensors undervoltage
Communication interface, functionSystem communication XF10 IN
Communication interface, connection typeSocket
Communication interface, connection technologyM8x1, D-coded according to EN 61076-2-114
Communication interface, number of pins/cores4
Communication interface, protocolAP
Communication interface, screenedyes
Power supply, functionIncoming electronics/sensors and load
Power supply, connection typePlugs
power supply, connection systemM8x1, A-coded to EN 61076-2-104
Power supply, number of pins/wires4
Note regarding operating voltageSELV/PELV fixed power supplies required Note voltage drop
Nominal DC operating voltage, electronics/sensors24 V
Permissible voltage fluctuations for electronics/sensors± 25%
Max. power supply2 x 4 A (external fuse required)
Intrinsic current consumption at nominal operating voltage for electronics/sensorsTypically 32 mA
Power failure bridging10 ms
Reverse polarity protectionyes
Electrical connection input, functionDigital input
Electrical connection input, connection type4x socket
Electrical connection input, connector systemM8x1, A-coded to EN 61076-2-104
Electrical connection input, number of connections/cores3
Number of inputs4
Characteristic for inputsTo IEC 61131-2, type 3
Switching levelSignal 0: <= 5 V Signal 1: >= 11 V
Switching logic for inputsPNP (positive switching) 2-wire sensors to IEC 61131-2 3-wire sensors to IEC 61131-2
Input debounce time0.1 ms 3 ms 10 ms 20 ms
Fuse protection of inputs (short circuit)Internal electronic fuse per module
Max. residual current of inputs per module0.8 A
Electrical isolation of inputs between channelsno
Electrical isolation of inputs between channel – internal communicationyes