Dimensions (W x L x H)42.2 mm x 76.5 mm x 125.8 mm
Grid dimension18.9 mm
Type of mountingWith H-rail
Max. number of modules10
Product weight145 g
Mounting positionVertical Horizontal
Note on ambient temperature-5 - 60°C for vertical installation
Storage temperature-20 °C ... 70 °C
Relative air humidity95 % Non-condensing
Degree of protectionIP20
Corrosion resistance class CRC0 - No corrosion stress
Vibration resistanceTransport application test with severity level 1 to FN 942017-4 and EN 60068-2-6
Shock resistanceShock test with severity level 1 to FN 942017-5 and EN 60068-2-27
Protection against direct and indirect contactPELV
LABS (PWIS) conformityVDMA24364 zone III
CE mark (see declaration of conformity)To EU EMC Directive
UKCA marking (see declaration of conformity)To UK RoHS instructions
KC markKC-EMV
ApprovalRCM trademark c UL us listed (OL)
Certificate issuing authorityUL E239998
Note on materialsRoHS-compliant
Material housingPA
Diagnostics via LEDForce mode Network fault Network status, port 1 Network status, port 2 Power supply, electronics/sensors Load power supply System fault Service required
Diagnostics via busWire break Short circuit PROFIsafe addresses different Parameterisation error Upper limit value violated Overtemperature Lower limit value not observed Undervoltage
Fieldbus interfaceEthernet
Field bus, protocolPROFINET IRT PROFINET RT
Fieldbus interface, functionBus connection incoming/outgoing
Field bus, connection type2x socket
Field bus, connection systemRJ45
Fieldbus interface, connection pattern00995789
Field bus, connection pattern8
Field bus interface, electrical isolationyes
Field bus interface, transmission rate100 Mbit/s
Max. address volume, inputs64 Byte
Fieldbus interface, max. address volume for inputs64 Byte
Note on inputs62 bytes with I/O diagnostic interface 62 bytes with status bits 64 bytes without diagnostics
Max. address volume, outputs64 Byte
Fieldbus interface, max. address volume for outputs64 Byte
Note on outputs62 bytes with I/O diagnostic interface 64 bytes with status bits 64 bytes without diagnostics
System parametersDiagnostic memory Fail-safe response Force mode System start
Module parametersChannel alarms for undervoltage Process value representation of analogue modules
Configuration supportGSDML file
Additional functionsLLDP MRP MRPD PROFINET FSU PROFINET I&MO..3, 1..3 retentive memory possible PROFINET shared device S2 system redundancy SNMP
Power supply, functionElectronics and sensors
Power supply, connection typeTerminal strip
Power supply, note on connection type> 4 A and UL 2x terminal strip for power supply
power supply, connection systemSpring-loaded terminal
Power supply, connection pattern00995847
Power supply, number of pins/wires4
Nominal DC operating voltage, electronics/sensors24 V
Permissible voltage fluctuations for electronics/sensors± 25%
Power supply, conductor diameter0.2 mm² ... 1.5 mm²
Power supply, note on conductor diameter0.2 - 2.5 mm² for flexible conductors without wire ferrule
Max. power supply8 A
Intrinsic current consumption at nominal operating voltage for electronics/sensorsTypically 75 mA
Power failure bridging20 ms
Reverse polarity protection24 V sensor supply against 0 V sensor supply