Dimensions (W x L x H)42.2 mm x 76.5 mm x 125.8 mm
Grid dimension18.9 mm
Type of mountingWith H-rail
Max. number of modules10
Product weight145 g
Mounting positionVertical Horizontal
Note on ambient temperature-5 - 60°C for vertical installation
Storage temperature-20 °C ... 70 °C
Relative air humidity95 % Non-condensing
Degree of protectionIP20
Corrosion resistance class CRC0 - No corrosion stress
Vibration resistanceTransport application test with severity level 1 to FN 942017-4 and EN 60068-2-6
Shock resistanceShock test with severity level 1 to FN 942017-5 and EN 60068-2-27
Protection against direct and indirect contactPELV
LABS (PWIS) conformityVDMA24364 zone III
CE mark (see declaration of conformity)To EU EMC Directive In accordance with EU RoHS Directive
UKCA marking (see declaration of conformity)To UK RoHS instructions
KC markKC-EMV
ApprovalRCM trademark c UL us listed (OL)
Certificate issuing authorityUL E239998
Note on materialsRoHS-compliant
Material housingPA
Diagnostics via LEDForce mode Module status Power supply, electronics/sensors Load power supply System fault
Diagnostics via busWire break Short circuit Parameterisation error Overflow buffer Upper limit value violated Transmission error Lower limit value not observed Undervoltage Watchdog/I/O status Requested function not supported Not ready for data exchange
Operator controlsDIL switch
Fieldbus interfacePROFIBUS
Field bus, protocolPROFIBUS DP
Fieldbus interface, functionBus connection incoming/outgoing
Field bus, connection typeSocket
Field bus, connection systemSub-D
Fieldbus interface, connection pattern00995638
Field bus, connection pattern9
Field bus interface, electrical isolationyes
Field bus interface, transmission rate1.5 Mbps 12 Mbit/s 187.5 kbit/s 19.2 kbit/s 3 Mbit/s 500 kbit/s 6 Mbit/s 9.6 kbit/s 93.75 kbit/s
Service interface, functionDiagnostics and parameterisation
Service interface, connection typeSocket
Service interface, connection technologyUSB 2.0 type B mini
Service interface, number of pins/wires5
Service interface, connection pattern00995868
Max. address volume, inputs64 Byte
Fieldbus interface, max. address volume for inputs64 Byte
Note on inputs62 bytes with I/O diagnostic interface 63 bytes with status bits 64 bytes without diagnostics
Max. address volume, outputs64 Byte
Fieldbus interface, max. address volume for outputs64 Byte
Note on outputs62 bytes with I/O diagnostic interface 64 bytes with status bits 64 bytes without diagnostics
System parametersDiagnostic memory Fail-safe response Force mode System start
Module parametersProcess value representation of analogue modules
Configuration supportGSD file
Power supply, functionElectronics and sensors
Power supply, connection typeTerminal strip
Power supply, note on connection type> 4 A and UL 2x terminal strip for power supply
power supply, connection systemSpring-loaded terminal
Power supply, connection pattern00995847
Power supply, number of pins/wires4
Nominal DC operating voltage, electronics/sensors24 V
Permissible voltage fluctuations for electronics/sensors± 25%
Power supply, conductor diameter0.2 mm² ... 1.5 mm²
Power supply, note on conductor diameter0.2 - 2.5 mm² for flexible conductors without wire ferrule
Max. power supply8 A
Intrinsic current consumption at nominal operating voltage for electronics/sensorsTypically 75 mA
Power failure bridging20 ms
Reverse polarity protection24 V sensor supply against 0 V sensor supply