Valve function3/2-way, closed, monostable
Type of actuationElectric
Operating pressure-13.05 psi ... 116 psi
DesignOn/off valve
Type of resetMechanical spring
CE mark (see declaration of conformity)To EU Explosion Protection Directive (ATEX)
Explosion protection certification outside the EUEPL Db (CN) EPL Gb (CN)
Certificate issuing authorityATEX: CML 17 ATEX 2046X CCC-Ex: 2020322307001726 IEC: IECEx CML 17.0030X
ATEX category gasII 1G
ATEX category dustII 1D
Explosion ignition protection type for gasEx ia IIC T6...T5 Gb
Explosion ignition protection type for dustEx ia IIIC T135°C Db
Explosion ambient temperature-40 °C<=Ta<=50 °C/65 °C
Degree of protectionIP65
Manual overrideDetenting
Flow directionNon-reversible
Symbol00991308
Duty cycle100%
Insulation material classH
Max. input power Pi-40°C ~+50°C T6 = 2.98W -40°C ~+65°C T135°C = 2.98W -40°C ~+65°C T5 = 2.98W -40°C ~+65°C T6 = 1W
Max. input voltage Ui31 V
Max. input current Ii0.67 A
Characteristic coil data24 V DC: 1.5 W
Effective internal inductivity LiNegligibly low
Effective internal capacitance CiNegligibly low
Permissible frequency fluctuations+/- 10%
Explosion protectionZone 0 (IEC-EX) Zone 1 (ATEX) Zone 1 (CN) Zone 21 (CN) Zone 22 (ATEX)
Operating mediumCompressed air to ISO 8573-1:2010 [7:4:4]
Note on operating and pilot mediumLubricated operation possible (in which case lubricated operation will always be required)
Corrosion resistance class CRC2 - Moderate corrosion stress
LABS (PWIS) conformityVDMA24364 zone III
Ambient temperature-20 °C ... 80 °C
Type of mountingCNOMO
Note on materialsRoHS-compliant