Vibration resistanceTransport application test with severity level 2 to FN 942017-4 and EN 60068-2-6
Note on vibration resistanceSG2 on wall mounting
Shock resistanceShock test with severity level 2 to FN 942017-5 and EN 60068-2-27
Note on shock resistanceSG2 on wall mounting
Valve terminal interfaceType 46, VTSA-F-CB
Reverse polarity protectionyes
Diagnostics via LEDDiagnostics per module Load power supply
Diagnostics per internal communicationLoad switch-off Communication fault Short-circuit/overload in output signal Electronics/sensors overvoltage Load overvoltage Electronics/sensors undervoltage Load undervoltage
Max. number of valve positions12 with bistable valves 24 with monostable valves
Max. number of valve coils24
Module code (hex/dec)0x3043/12355d
Module parametersActivation of diagnostics in case of overload/short circuit Condition counter limit value/actual value Configuration of voltage monitoring load supply PL Response in error state
Internal cycle time< 1 ms
Dimensions (W x L x H)70.5 mm x 142 mm x 102.6 mm
Fuse protection (short circuit)Internal electronic fuse protection per valve output
Intrinsic current consumption at nominal operating voltage for electronics/sensorsTypically 40 mA
Intrinsic current consumption at nominal operating voltage loadTypical 17 mA
Note regarding operating voltageSELV/PELV fixed power supplies required Note voltage drop
Nominal DC operating voltage, electronics/sensors24 V
Nominal operating voltage DC of load24 V
Power failure bridging10 ms
Isolation channel - internal busYes, when using an additional power supply for the valves
Potential separation between the supply voltages electronics/sensor technology and load/valvesYes
Pollution degree2
Permissible voltage fluctuations for electronics/sensors± 25%
Permissible voltage fluctuation of load± 10%
Undervoltage load/valves (diagnostic message)≤21.6 V
Corrosion resistance class CRC0 - No corrosion stress
LABS (PWIS) conformityVDMA24364-B2-L
Storage temperature-20 °C ... 70 °C
Relative air humidity5 - 95% Non-condensing
Protection classIII
Overvoltage categoryII
Ambient temperature-20 °C ... 50 °C
Note on ambient temperatureObserve ambient temperature derating according to IEC 61131-2:2017
Nominal altitude of use<= 2000 m ASL (> 79.5 kPa)
Max. installation height3500 m
Note on max. installation height> 2000 m ASL (< 79.5 kPa) Observe ambient temperature derating according to IEC 61131-2:2017
Product weight1238 g
Electrical controlFieldbus
Communication interface, protocolAP
Type of mountingVia through-hole for M6 screw
Note on materialsRoHS-compliant Free of halogen Free of phosphoric acid ester
Material coverZinc die-cast metal, powder-coated
Material sealsNBR PUR
Material housingAluminium
Material screwsNickel-plated steel