Symbol00995410
ApprovalRCM trademark c UL us listed (OL)
CE mark (see declaration of conformity)To EU EMC Directive In accordance with EU RoHS Directive
UKCA marking (see declaration of conformity)To UK RoHS instructions
KC markKC-EMV
Note on materialsRoHS-compliant
Measured variableRelative pressure
Measurement methodPiezoresistive pressure sensor
Start value for pressure measuring range-14.5 psi
End value for pressure measuring range145 psi
Overload pressure217.5 psi
Operating mediumCompressed air to ISO 8573-1:2010 [7:4:4] Inert gas
Note on operating and pilot mediumLubricated operation possible
Media temperature0 °C ... 50 °C
Ambient temperature0 °C ... 50 °C
Resolution ADC12 bit
Accuracy in ± % FS1.5 %FS
Repetition accuracy in ± %FS0.3 %FS
Temperature coefficient in ± %FS/K0.05 %FS/K
Switching output2 x PNP or 2 x NPN, switchable 2xPNP
Switching functionFreely programmable
Switching element functionN/C or N/O contact, switchable
Max. output current100 mA
Analogue output0 - 10 V 4 - 20 mA 1 - 5 V
Rise time3 ms
Max. load resistance current output500 Ohm
Min. load resistance voltage output10 kOhm
Short circuit current ratingyes
ProtocolIO-Link®
IO-Link, Protocol versionDevice V 1.1
IO-Link, ProfileSmart sensor profile
IO-Link, Function classesBinary data channel (BDC) Process data variable (PDV) Identification Diagnostics Teach channel
IO-Link, communication modeCOM2 (38.4 kBaud)
IO-Link, SIO-Mode supportYes
IO-Link, Port classA
IO-Link, Process data length OUT0 bytes
IO-Link, Process data length IN2 bytes
IO-Link, Process data content IN14 bit PDV (pressure measurement value) 2 bit BDC (pressure monitoring)
IO-Link, Min. cycle time3 ms
IO-Link, Data storage required500 Byte
Operational voltage range DC20 V ... 30 V
Reverse polarity protectionFor all electrical connections
Electrical connection 1, connection typePlugs
Electrical connection 1, connector systemM12x1, A-coded to EN 61076-2-101
Electrical connection 1, number of connections/cores4
Electrical connection 1, type of mountingNot rotatable
Electrical connection 1, compatible type of mountingCompatible with latching lock Compatible with rotatable screw-type lock
Electrical connection 1, connection pattern00995386
Type of mountingWith H-rail
Mounting positionoptional
Pneumatic connectionG1/8
Product weight70 g
Material in contact with the mediumFPM PA-reinforced High-alloy stainless steel
Display typeIlluminated LCD LED
Displayable unitsMPa bar inH2O inHg kPa kgf/cm² mmHg psi
Setting optionsIO-Link® Teach-in Via display and keys
Protection against tamperingIO-Link PIN code
Setting range threshold value0 % ... 100 %
Setting range hysteresis0 % ... 90 %
Degree of protectionIP65 IP67
Corrosion resistance class CRC2 - Moderate corrosion stress
LABS (PWIS) conformityVDMA24364-B1/B2-L