DesignAngular
Based on standardVDI/VDE 3845 (NAMUR)
ApprovalRCM trademark c UL us - Recognized (OL)
CE mark (see declaration of conformity)To EU EMC Directive To EU Explosion Protection Directive (ATEX) In accordance with EU RoHS Directive
UKCA marking (see declaration of conformity)To UK RoHS instructions
Explosion protectionZone 2 (ATEX) Zone 2 (UKEX) Zone 22 (ATEX) Zone 22 (UKEX)
ATEX category gasII 3G
Explosion ignition protection type for gasEx ec IIC T5 Gc X
ATEX category dustII 3D
Explosion ignition protection type for dustEx tc IIIC T90°C Dc X
Explosion protection certification outside the EUEPL Dc (GB) EPL Gc (GB)
Explosion ambient temperature-20°C <= Ta <= +80°C
Note on materialsRoHS-compliant
Measured variableRotation angle
Measuring principleMagnetic Hall
Ambient temperature-20 °C ... 80 °C
Analogue output4 - 20 mA
Repetition accuracy analogue output in ± °1 deg
Short circuit current ratingyes
Overload protectionAvailable
Operational voltage range DC15 V ... 30 V
No-load supply current12 mA ... 20 mA
Reverse polarity protectionFor all electrical connections
Electrical connectionScrew terminal Plug-in
Connectable nominal cross section conductor2.5 mm²
Cable fittingM20
Permissible cable diameter5 mm ... 13 mm
Max. cable length30 m
Mounting positionoptional
Product weight1000 g
Material housingWrought aluminium alloy
Position indicatorRed/green
Setting optionsTeach-in Teach-in via electrical connection
Setting range of angular detection0 deg ... 270 deg
Degree of protectionIP65
Insulation voltage50 V
Immunity to surge0.8 kV
Protection classIII
Corrosion resistance class CRC3 - high corrosion stress
LABS (PWIS) conformityVDMA24364-B2-L
Pollution degree3